Semester : SEMESTER 6
Subject : Power System Analysis
Year : 2018
Term : APRIL
Scheme : 2015 Full Time
Course Code : EE 306
Page:2
^
(0)
10
11 (a)
(0)
12
13
C6811 Pages: 3
Find the expression for three phase power in terms of symmetrical components.
A synchronous generator and motor are rated 30MVA, 13.2kV and both have sub-
transient reactances of 20%. The line connecting them has a reactance of 10% on the
base of the machine ratings. The motor is drawing 20,000kW at 0.85 power factor
lagging at a terminal voltage of 12.8 kV when a symmetrical three phase fault occurs
at the motor terminals. Find the sub-transient current in the generator, motor and
fault.
A three phase generator is connected to a star-delta transformer as shown in the
figure.
ro
07
یہہ
॥ ॥
1 م26
The reactance values referred to a common base are :
Zi 22 20
Alternator 10.1 10.1 10.05
Transformer 10.05 10.05 10.05
Transmission line 10.4 10.4 10.8
Determine the fault current when a double line to ground fault occurs at point ‘P’ at
the mid-point of the line if the alternator neutral is grounded. Assume that the
generator is not loaded
Obtain the symmetrical components of the following set of unbalanced currents
I, = 1.61 250°, 1, = 1.0L. 180°, I, = 0.9L 132°
PART C
Answer any two full questions, each carries 10 marks.
Explain the computational procedure for load flow solution using fast decoupled load
flow method.
Figure shows a three bus power system. The impedance of each line is (0.026 + j0.11)
pu.
೦
bo
2
7
The bus details are given in the table below
| Bus | Po(pu) | Qe(pu)
Assuming a flat voltage start, find the voltages and bus angles at the buses at the end
of the first iteration using Gauss-Siedel method.
Page 2 of 3
(4)
(10)
(6)
(4)
(10)
(10)